Rabu, 13 April 2016

SEW 1120 ER Earth Resistance Testers


SEW 1120 ER Earth Resistance Testers

FEATURES
  • Capable of measuring earth resistance and earth voltage.
  • 2mA measuring current permits the testing of earth resistance without tripping earth leakage current  breakers in the circuit under test.
  • The leads are supplied as standard accessories for simplified two-wire measuring system.
  • 0Ω adjustment.
  • Battery operated.
  • Data hold function.
  • Low battery indication.
  • Calibration performed with supplied test leads.
SPECIFICATIONS
Measuring ranges
 Earth resistance  
 0-20Ω / 0-200Ω / 0-2000Ω
 Earth voltage  
 0-200 Vac(40-500Hz)
 Accuracy
 Earth resistance  ±(2%rdg+2dgt) 
 or ±0.1Ω,  which is greater
 Earth voltage  ±(1%rdg+2dgt)
 Earth resistance
 resolution

 0-20Ω : 0.01Ω   
 0-200Ω : 0.1Ω   
 0-2000Ω : 1Ω
 Measuring system
 Earth Resistance by constant 
 current inverter 820Hz approx. 2mA
 Display
 3½ digit (2000 counts)
 0Ω adjustment
 ˇ
 Open circuit 
 indication

 LED will be unlit
 Low battery 
 indication

 “  “symbol appears  on the display
 Data hold 
 indication

 “  “symbol appears on the display
 Over range 
 indication

 “1”(MSD)
 Dimensions
 175(L) × 85(W) × 75(D)mm
 Weight
 (battery included)

 Approx. 600g
 Power source
 1.5V (AA) × 8    
 Safety standards
 IEC/EN 61010-1 CAT III 200V
 IEC 61557-1 IEC 61557-5
 EN 61326-1