HIOKI
3197 Power Quality Analyzer
3-Phase
4-Wire Portable Power Quality Analyzer to Detect, Measure and Record Power
Quality Issues, Harmonics, Demand, Inrush and Power Transients
Hioki
portable power meters and analyzers are best in class power measuring
instruments for measuring single to three-phase lines with a high degree of
precision and accuracy. The 3197 is a handheld power quality analyzer for
monitoring and recording power supply anomalies, allowing their causes to be
quickly investigated.
Note:
Optional current sensor is necessary to measure current or power parameters.
Overview
- Single-phase 2-wire/single-phase
3-wire/three-phase 3-wire/three-phase 4-wire
- Catch power quality problems on
the fly, before they catch you
- Record measurement data on
internal memory for easy transfer to a PC via USB
- Analyze measurement data on a
bundled PC aplication software.
Specification
Measurement line
type
|
Single-phase
2-wire, single-phase 3-wire, three-phase 3-wire, three-phase 4-wire
|
Measurement range
|
[Voltage] 600.0 V
AC, [Current] 500.0 mA to 5.000 kA AC (depends on current sensor in use),
[Power] 300.0 W to
9.00 MW (depends on combination of current range and line type)
|
Basic accuracy
|
Voltage: ±0.3 %
rdg. ±0.2 % f.s.
Current: ±0.3 %
rdg. ±0.2 % f.s. + current sensor accuracy
Active power: ±0.3
% rdg. ±0.2 % f.s. + current sensor accuracy (at power factor=1)
|
Measurement items
|
1. RMS Voltage and
Current (200 ms calculation)
2. Voltage (1/2)
RMS: one cycle calculation refreshed every half cycle
3. Current (1/2)
RMS: half-cycle calculation
4. Frequency
5. Active Power/
Reactive Power/ Apparent Power/ Power Factor/ Displacement Power Factor/
Active or Reactive Energy Consumption
6. Demand (Active
or Reactive power)
7. Up to 50th
Harmonic Analysis (Time series measurement or recording is not available)
8. Peak Voltage and
Current
9. Total harmonic
voltage distortion ratio
10. Voltage
Unbalance Factor
11. K Factor (Time
series recording is not capable)
12. Total harmonic
current distortion ratio (Time series recording is not available)
|
Event Detection
|
1. Voltage Swells
(Rise), Voltage Dips (Drop), Interruptions: RMS value detected using voltage
(1/2) measured every half cycle
2. Inrush Current:
RMS value detected using current (1/2) every half cycle
3. Transient
Overvoltage: 50 Vrms or more detection, 10 to 100 kHz
4. Timer: Detect
events at preset intervals
5. Manual: Detect
events when keys are pressed
|
Number of
Recordable Events
|
50 event waveforms,
20 event voltage fluctuation graphs, 1 inrush current graph, 1000 event
counts
|
Interfaces
|
USB 2.0
(Communication with the PC)
|
Display
|
4.7-inch color STN
LCD
|
Power supply
|
AC adapter 9418-15
(100 - 240 V, 50/60 Hz), Battery pack 9459, Continuous use 6 hr (LCD
Back-light auto-OFF 5 min.), 23 VA max.
|
Dimensions and mass
|
128 mm (5.04 in)W ×
246 mm (9.69 in)H × 63 mm (2.48 in)D, 1.2 kg (42.3 oz) (with Battery pack)
|
Accessories
|
Voltage cord
L9438-55 ×1 (Black ×4), AC adapter 9418-15 ×1, Power cord ×1, Battery pack
9459 ×1, Input terminal labels ×1, Input cord labels ×1, Strap ×1,
Instruction manual ×1, Measurement guide ×1, USB Cable ×1, CD-R (Applications
software) ×1, Carrying case ×1
|
0 komentar: