KYORITSU 4106 Earth Resistance & Resistivity Tester
- High test current up to 80mA yielding resolution of 0.001Ω on 2Ω range.
- Advanced Filtering method (based on FFT Fast Fourier Transform) reduces noise interference for obtaining stable measurements.
- Automatic and Manual selection of the Test Current Frequency in four bands (94/105/111/128Hz). In Automatic mode, KEW 4106 will select the most suitable Frequency.
- Several sub-results can be shown on the display: Resistance of the Auxiliary Earth Spikes, Frequency of Test Current, Voltage and Frequency of Interference (noise), Residual Resistance Rk, etc.
- Warning for excessive noise and high Auxiliary Earth Spikes resistance.
- Large Graphic Display with backlight for readings in poorly illuminated areas.
- Up to 800 measurement results can be saved in the memory and recalled on the display.
- The stored results can be transferred to a PC using the "KEW Report" software and a USB adaptor (Model 8212-USB) which are included.
- Robust design with IP54 protection.
Function
|
Range
|
Resolution
|
Measuring range
|
Accuracy
|
Earth resistance Re (Rg at ρ measurement) |
2Ω |
0.001Ω |
0.03~2.099Ω |
|±2%rdg±0.03Ω |
20Ω |
0.01Ω |
0.03~20.99Ω |
|±2%rdg±5dgt (*1) |
|
200Ω |
0.1Ω |
0.3~209.9Ω |
||
2000Ω |
1Ω |
3~2099Ω |
||
20kΩ |
10Ω |
0.03~20.99kΩ |
||
200kΩ |
100Ω |
3~209.9kΩ |
||
Auxiliary earth resistance Rh, Rs |
|
|
|
8% of Re+Rh+Rs |
Earth resistivity ρ |
2Ω |
0.1Ω•m~1Ω•m Autoranging |
0.2~395.6Ω•m |
ρ=2×π×a×Rg (*2) |
20Ω |
0.2~3956Ω•m |
|||
200Ω |
20~39.56kΩ•m |
|||
2000Ω |
0.2~395.6kΩ•m |
|||
20kΩ |
2.0~1999kΩ•m |
|||
200kΩ |
||||
Series interference voltage Ust (A.C only) (*3) |
50V |
0.1V |
0~50.9Vrms |
|±2%rdg±2dgt (50/60Hz) |
|±3%rdg±2dgt (40~500Hz) |
||||
Frequency Fst |
Autoranging |
0.1Hz 1Hz |
40Hz~500Hz |
|±1%rdg±2dgt |
Measuring method |
Earth resistance: Fall-of-potential method (currents and voltages measured via the Probes) Measurement method of Earth Resistivity (ρ): Wenner 4-pole method Series interference voltage (earth voltage): RMS Rectifier (between the E-S Terminals) |
|||
Memory capacity |
800 data |
|||
Communication Interface |
Model 8212-USB Optical Adaptor |
|||
LCD |
Dot-matrix 192×64 monochrome |
|||
Over-range Indication |
"OL" |
|||
Overload Protection |
between E-S(P) and between E-H(C) terminals AC280V / 10 sec. |
|||
Withstand voltage |
between the electrical circuit and enclosure AC3540V(50/60Hz) / 5 sec. |
|||
Applicable standards |
IEC 61010-1 CAT.III 300V, CAT.IV 150V Pollution degree 2 IEC 61010-031, IEC 61557-1, 5, IEC 61326-1 (EMC), IEC 60529 (IP54) |
|||
Power source |
DC12V : sizeAA manganese dry battery (R6P) × 8 (Auto power off: approx. 5 minutes) |
|||
Dimensions |
167(L) × 185(W) × 89(D) mm |
|||
Weight |
approx. 900g (including batteries) |
|||
Accessories |
7229A (Earth precision measurement), 7238A (Simplified measurement test leads), 8032 (Auxiliary earth spikes [2 spiks/set])×2 sets (4 spikes in total), 8200-04 (Cord reel [4 pcs])×1 set, 8212-USB (USB adaptor with "KEW Report(Software)"), 9121 (Shoulder strap), 9125 (Carrying case), R6P×8, Instruction manual, Calibration certificate |
|||
Optional |
8212-RS232C (RS232C adaptor with "KEW Report(Software)") |
(*2) Depending on the measured Rg. Interval [a] between auxiliary earth spikes is 1.0~30.0m
(*3) This instrument is NOT designed to measure line voltages on commercial powers.