276S HD High Voltage Testers
H.V. Detector
230mm to 880mm
FEATURES :
Telescopic, compact, light-weight : Length : from 230mm to 880mm. Weight : Approx. 155g
High-voltage detectable : The equipment, whether in stretched state is
available for voltage detection in high-tension circuits ( 3.3kV, 6.6kV
and 24kV) whether the wires involved are naked or insulated.
Low-voltage detectable : The equipment can be used for voltage detection
in low-tension circuits ( 80V ~ 600V) by holding the nameplate portion
of the detecting head. Before-use check can easily be done by plugging
in an AC 100V plug socket, without using a tester.
Easy to recognize
indication : Intermittent lighting in red of a high intensity
light-emitting diode and intermittent audible sound of an electronic
buzzer are readily recongnizable at a full daylight, noisy location.
Waterproof : The detecting head, being tightly enclosed, is free from any trouble due to dust, dirt, water or the like.
Dielectric strength :
( a) Between Sensing tip ~ Grip portion : 50kVAC, 1 min ( The detector has to be stretched) .
( b) Between Sensing tip ~ Nameplate portion : 4kV AC, 1 min.
Construction : Waterproof ( detecting head impervious to water) .
Insulation resistance : Measure the insulation resistance with the high
voltage insulation tester. The areas we measure are the same as
dielectric strength test.
( a) Between Sensing tip ~ Grip portion :
1kV ( The detector has to be stretched) . The insulation resistance has
to be more than 2000M Ohm.
( b) Between Sensing tip ~ Nameplate portion : 1kV. The insulation resistance has to be more than 2000M Ohm.
Leakage current test : Put high voltage on the parts listed below.
( a) Between Sensing tip ~ Grip portion : 50kV AC, 1 min ( The detector
has to be stretched) . The leakage current has to be 100uA or less than
100uA.
( b) Between Sensing tip ~ Nameplate portion : 4kV AC, 1 min. The leakage current has to be 100uA or less than 100uA
Meets EN 61010-1, EN50081-1, EN 55082-1, EN 55022, EN 61000-4-2, EN 61000-4-3
This model 276 HD detects the presence of voltage in AC lines. An
elongate insulation rod permits checking of high tension circuits at
safe distance for voltage.
The equipment is compact, light weight,
and easy to handle, and is also available for voltage detection in
low-tension circuits.
SPECIFICATIONS
Working Voltage Range H.V. : 3kV ~ 24kV AC ...... hold grip portion to detect.
L.V. : 80V ~ 600V AC ...... hold anmeplate portion to detect.
Frequency 50Hz / 60Hz
Operation Test ( Initial voltage) ( a) When stretched, hold the grip
portion. Put the sensing tip in contact with the voltage : 250V AC + / -
50V the LED and buzzer should work.
( b) When retracted, hold the
nameplate portion. Put the sensing tip in contact with the voltage : 80V
AC or below the LED and buzzer should work.
Operation start
distance Distance at which operation starts when front metal is brought
near dia. 5mm O.C. wire with grip portion meld by hand.
Where 24kV / dia. 3mm ( voltage to ground) ...... abt 20 cm.
Where 6.6kV / dia. 3mm ( voltage to ground) ...... abt 3 cm.
Where 3.3kV / dia. 3mm ( voltage to ground) ...... abt 1 cm.
Woking temperature rang -10 degree C ~ + 50 degree C
Battery 2 button-cells LR44 ( 1.5V)